Room Pressure Transmitter c/w LCD Current Type

Discover the Room Pressure Transmitter c/w LCD Current Type, designed for precise pressure monitoring and control. Featuring an easy-to-read LCD display, reliable current output, and accurate room pressure measurement. Ideal for cleanrooms, HVAC systems, and industrial applications. Ensure optimal performance with our advanced room pressure sensor technology.

Key Features

  • Three-line display with illumination, cutout approx.
  • 70 x 40 mm (W x H).
  • For displaying ACTUAL pressure.
  • As well as automatic zero point calibration.

৳ 0.00

Description

Room Pressure Transmitter c/w LCD Current Type | 1301-7112-4110-100-S+S REGELTECHNIK

The Room Pressure Transmitter c/w LCD Current Type 1301-7112-4110-100 by S+S REGELTECHNIK is an advanced pressure monitoring transmitter designed to ensure precise and reliable measurements in critical environments. Featuring a user-friendly LCD display, this transmitter provides real-time monitoring of room pressure, making it an essential for HVAC systems, cleanrooms, laboratories, and industrial facilities.

Room Pressure Transmitter c/w LCD Current Type Key Features:

  • Accurate Pressure Measurement: Ensures precise room pressure monitoring.
  • LCD Display: Provides clear real-time readings.
  • Current Output: Stable and reliable 4-20mA current output.
  • High-Quality Build: Durable construction for long-lasting performance.
  • Easy Installation: Designed for quick and efficient setup.

Room Pressure Transmitter c/w LCD Current Type Applications:

  • Cleanrooms: Maintain contamination-free environments.
  • HVAC Systems: Optimize heating, ventilation, and air conditioning.
  • Laboratories: Ensure controlled and stable pressure conditions.
  • Hospitals: Maintain critical room pressures in surgical and isolation rooms.

Why Choose S+S REGELTECHNIK?

S+S REGELTECHNIK is renowned for delivering high-performance sensors and transmitters, ensuring reliability, accuracy, and efficiency in pressure monitoring solutions. The 1301-7112-4110-100 Room Pressure Transmitter is a testament to their commitment to quality engineering.

For enhanced room pressure control and seamless integration into your systems, choose the Room Pressure Transmitter c/w LCD Current Type 1301-7112-4110-100 by S+S REGELTECHNIK.

PREMASGARD® 711x

The calibratable PREMASGARD® 711x compact pressure sensors (series) are equipped with eight switchable measuring ranges and equipped with optional display (eight devices in one) and are used to measure above-atmospheric, below-atmospheric, or differential pressures in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and precision. The pressure transmitters feature a pushbutton for manual zero point calibration or an automatic zero point calibration function as well as an adjustable offset.

Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement or for triggering frequency converters. Media measured with these pressure transducers are clean air (non-precipitating), or other gaseous non-aggressive, non-combustible media. The pressure sensor has eight selectable measuring ranges, thereby minimising the diversity of types and inventory levels while covering a greater range of applications. The differential pressure sensor is supplied including connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).

Contact us today our website-techhomesbd for buying best Room Pressure Transmitter c/w LCD Current Type.

Specifications

Power supply: 24 V AC (± 20 %); 15…36 V DC for U variant
15…36 V DC for I variant,
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance: Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant
Load resistance: RL > 5 kOhm for U variant
Power consumption:
< 2 VA ⁄ 24 V DC, < 3.5 VA ⁄ 24 V AC
Measuring ranges:
multi-range switching with 8 switchable measuring ranges (see table)
Output signal: 0 -10 V or 4…20 mA
Electrical connection:
2- or 3-wire connection
Media temperature:
–20…+50 °C
Pressure connection:
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm), metal pressure connection nozzles
Type of pressure:
differential pressure
Medium:
clean air and non-aggressive, non-combustible gases
Accuracy:
Type 7112 (25 Pa): ± 1 Pa
Type 7110 (100 Pa): ± 2 Pa
Type 7111 (1000 Pa): ± 5 Pa
Type 7115 (5000 Pa): ± 25 Pa
compared to the calibrated reference device
Sum of Linearity+hysteresis: < ± 1 % of final value
± 2 % of final value for pressure ranges < ± 250 Pa
Temperature drift values: ± 0.1 % /°C
± 0.3 % /°C for pressure ranges < 250 Pa
Zero point offset: < ± 0.7 % of final value
± 1.4 % of final value for pressure ranges < 250 Pa
Above- ⁄ below atmospheric pressure
max. ± 100 hPa
Signal filtering:
switchable 1 s ⁄ 10 s
Enclosure: plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
Dimensions:
126 x 90 x 50 mm (Tyr 2)
Electrical connection:
0.14 -1.5 mm², via plug-in screw terminal
Cable gland: M 16 x1.5; including strain relief
Air humidity: < 95 % r. H., non-precipitating air
Standards: CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
Equipment:
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying ACTUAL pressure and for adjusting the automatic zero point calibration

 

What is the Price of Room Pressure Transmitter c/w LCD Current Typein Bangladesh?

Datasheet

Reviews (0)
0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Room Pressure Transmitter c/w LCD Current Type”

Your email address will not be published. Required fields are marked *

You have to be logged in to be able to add photos to your review.

We're happy to help

View your recourse ..