FSB-200 Beam Smoke Detector
The Notifier FSB-200 Beam Smoke Detector offers reliable fire protection for large, open areas. Ideal for atriums, warehouses, and more, this intelligent, addressable detector provides early warning of smoke threats.
Key Features
- UL 268 Listed, ULC S529 Certified.
- Transmitter/receiver built into the same unit.
- Six user-selectable sensitivity levels.
- Protection Range: 16′-328′ (BEAMLRK for >230′).
- Removable plug-in terminal blocks.
- Digital display — no special tools required.
৳ 0.00
Description
FSB-200 Beam Smoke Detector
The FSB-200 Beam Smoke Detector is a type of projected beam smoke detector designed for large open areas such as warehouses, atriums, or auditoriums. It uses a projected beam of light to detect smoke by analyzing the light’s attenuation or obscuration caused by smoke particles in the air.
In larger or taller spaces, beam smoke detectors provide a more sophisticated fire detection solution. They cover a larger area and reduce false alarms making them popular for many individuals. Selection of Beam Smoke Detectors based on its coverage area type and maintenance are important to ensure safety.
FSB-200 Beam Smoke Detector Features
- Automatic gain control compensates for dust buildup.
- Optional remote test station.
- Paintable cover.
- Integral sensitivity test filter (FSB-200S only, external power required)
- Sensitivity filter (incremental scale on reflector).
- Local alarm test switch.
- Local alarm reset switch.
- Remote test/reset (compatible with RTS151/RTS151KEY)
- BEAMLRK: Long-range kit for distances over 230′ (70 m)
- BEAMMMK: Multi-mount kit for ceiling or wall mounting
- BEAMHK/BEAMHKR: Heater kits for condensation prevention
- UL 268 Listed, ULC S529 Certified.
- Transmitter/receiver built into the same unit.
Specifications
Model: FSB-200
Brand: Notifier by Honeywell
Temperature: –22°F to 131°F (–30°C to 55°C).
Humidity: 10 – 93% RH non condensing
Voltage: 15 to 32 VDC.
Standby Current (24 VDC): ≤ 2 mA
(LED flashing, SLC @ 24 V)
Alarm Current (LED on): 8.5 mA maximum
Trouble Current (LED on): 4.5 mA maximum
Ali External Supply (FSB-200S only): Voltage — 15 to 32 VD
Current — 0.5 A maximum.
Gnment Current: 20 mA maximum
Remote Output (Alarm): Voltage – 15 to 32 VDC (Output voltage same as device input voltage)
Typical Output Current Range: 6 to 15 milliamperes (limited by a 2.2 kilo ohm resistor)
Heater Kit BEAMHK: Voltage – 15 to 32 V; Current – 92 mA
Power Consumption: 1.6 W (24 V), 3.0 W max (32 V, heater only)
BEAMHKR Reflector Heater Kit: Operating Voltage Range of 15 to 32 Volts
Shipping Weight: 3.7 lbs (1.68 kg)
Detector Dimensions: 10.0 inches high x 7.5 inches wide x 3.3 inches deep (254 mm x 191 mm x 84 mm)
Reflector Dimensions for Applications up to 230 feet (70 meters): 7.9 inches x 9.1 inches (200 mm x 230 mm)
Reflector Dimensions for Applications Beyond 230 feet (70 meters): 15.7 inches x 18.1 inches (400 mm x 460 mm)