HPF24S6E Auxiliary Power Supply
The HPF24S6 and HPF24S8 are compact, cost-effective, 6-amp or 8-amp remote power supplies with a battery charger built in. They may be connected to any 12- or 24-volt Fire Alarm Control Panel (FACP) or may stand alone. HPF24S6E Auxiliary Power Supply include Notification Appliance (bell) Circuit (NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to support 24-volt system accessories.
The HPF24S6E Auxiliary Power Supply supply provides regulated and filtered 24 VDC power to four Notification Appliance Circuits configured as either four Class B (Style Y) or Class A (Style A, with ZNAC-4 option module). Alternately, the four outputs may be configured as all non-resettable or all resettable or two non-resettable and two resettable. They also contains a battery charger capable of charging up to 18 Amp Hour batteries.
Benefits & Specifications
- Instantaneous switchover to standby battery (if equipped) when AC fails, maintaining power to all attached devices without intervention.
- Strobe signal “passes through” allowing syncing of large systems.
- UL Listed NAC Synchronization using System Sensor, Wheelock or Gentex (Commander Series) appliances.
- Cascade up to 10 power supplies (four with Gentex) with strobe timing maintained.
- Operates as a sync follower or a sync generator (default).
- Contains two, fully-isolated input/control circuits (triggered from FACP Notification Appliance Circuit [NAC expander mode] or jumpered permanently on [standalone mode]).
- HPF24S6E Auxiliary Power Supply to internally house addressable SLC control module for alarm activation.
- Four Class B (Style Y) or four Class A (Style Z) (with ZNAC- 4 Module) Notification Appliance Circuits.
- 6.0A or 8A (depending on model) full load output (3.0 A maximum per circuit) in NAC expander mode (UL 864).
- 4.0A or 6.0Acontinuous output in stand-alone mode (UL 1481).
- In stand-alone mode, output power circuits may be configured as resettable (reset line from FACP required) or non resettable or a mix of two and two.
- Fully regulated and filtered power output (optimal for powering four-wire smoke detectors, annunciators and other system peripherals requiring regulated/filtered power).
- Power-limiting technology meets UL power-limiting requirements.
- Form-C normally-closed trouble relay.
- Fully supervised power supply, battery and Notification Appliance Circuits.
- Selectable earth fault detection.
- AC trouble report selectable for immediate or 8 hour delay.
- Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power).
- Requires input trigger voltage of 9.0 – 32 VDC.
- Self-contained in compact, lockable cabinet (15″ [38.1 cm] H x 14.5″ [36.8 cm] W x 2.75″ [7.0 cm] D).
- Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batteries.
- Battery charger may be disabled via dip switch for applications requiring larger batteries.
- Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1 mm2) wire.