BELIMO VRU-M1R-BAC
The BELIMO VRU-M1R-BAC is an advanced actuator designed for HVAC systems to regulate air and fluid flow. It ensures accurate modulation, optimizing system efficiency and energy management. Its durable construction and dependable performance make it ideal for both residential and industrial applications requiring continuous, reliable environmental control.
Key Features
- Integrated diaphragm Δp‑sensor for polluted media
- Hybrid analogue and digital control (0.5‑10 V + bus)
- Communication via BACnet MS/TP, Modbus RTU, MP‑Bus
- Functional differential pressure range ±75 Pa (‑0.3…0.3 in WC) belimo.com+1
- Installation‑position independent, no zeroing required belimo.com+1
- Compatible with VST actuators and room‑pressure or VAV applications
৳ 0.00
Description
In demanding HVAC and building‑automation environments—such as clean rooms, hospital suites or pressure‑controlled zones—precise control of air‑volume, duct pressure and room pressure is essential. The Belimo VRU‑M1R‑BAC addresses this by combining a high‑accuracy diaphragm differential‑pressure sensor (capable of ±75 Pa measurement) with a fully featured controller that supports analog inputs/outputs and open‑protocol bus communication (BACnet, Modbus, MP‑Bus). This means one module can both sense and control, reducing the need for separate sensors, signal converters and controllers. For example, in a sensitive environment with contaminated media (dust, fibres, etc), the M1R sensor is designed to operate reliably, making it suitable for room‑pressure cascades or VAV boxes in healthcare or laboratory ventilation. Compared to simpler VAV controllers that only accept 0‑10 V inputs, the VRU‑M1R‑BAC’s hybrid bus support enables advanced monitoring, diagnostics and integration into BMS systems. Its installation‑position independence (no zeroing needed) saves commissioning time, and compatibility with Belimo VST actuators ensures seamless system building. Whether controlling a VAV unit, maintaining negative‑pressure rooms or managing fan speed via pressure loop, this unit offers professional, future‑ready performance.
Specifications
- Nominal voltage: AC/DC 24 V. belimo.com+1
- Nominal voltage range: AC 19.2…28.8 V / DC 21.6…28.8 V. belimo.com+1
- Power consumption in operation: 1.5 W. belimo.com+1
- Wiring sizing: 2 VA plus connected VST actuator; inrush current Imax 20 A @ 5 ms including actuator. belimo.com+1
- Control / communication types: BACnet MS/TP, Modbus RTU, MP‑Bus; analog input 0.5…10 V or 2…10 V. belimo.com+1
- Functional differential pressure range: ‑75…+75 Pa (‑0.3…0.3 in WC) for room‑pressure version. belimo.com+1
- Accuracy differential pressure: ±0.25 Pa (±0.001 in WC) in specified range. belimo.com
- Burst pressure: ±7 kPa (±28 in WC). belimo.com+1
- Installation position: Independent (no zeroing required) – simplifies field installation. belimo.com+1
- Connection: Terminals 2.5 mm² for supply and control. belimo.com+1
- Sensor tube connection: Nipple diameter ~5.3 mm (for pressure hose 3/16″) for the pressure tube. belimo.com+1
- Ambient conditions measuring air: 0…50 °C / 5…95% RH non‑condensing for sensor. belimo.com
The Belimo VRU‑M1R‑BAC is imported into Bangladesh via specialist HVAC and building‑automation distributors and is priced in line with high‑end VAV/pressure control modules. Its premium features—integrated Δp sensor, multi‑protocol communication and modular architecture—place it in the professional system grade rather than commodity pricing. Local buyers should expect cost to reflect import duties, brand value and system‑integration capability.

Reviews